4.5 Function–initiating and diagnostic parameters
4-134
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 4-2 Function–initiating parameters, continued
Parameters
No. EffectiveUnitsMax.StandardMin.Name
1084 Start motor data optimization (ARM) 0 0 1 – Immedi-
ately
... starts the ”motor data optimization” function, which is set in P1083.
0 Inactive or exited fault–free
1 Start motor data optimization
Note:
At the end, 0 or a fault code is automatically written into the parameter.
Fault code:
–2 A pulse frequency (P1100) of 4 kHz or 8 kHz is required
–3 Controller/pulse enable missing
–4 Speed setpoint <> 0
–5 Motor is presently being changed–over
–6 Error when determining the leakage inductance (result) < 0)
–7 V/f mode is active
–8 The incorrect motor was selected because of the motor changeover
–9 Parameterized maximum speed is too low for the measurement
–11 Changeover speed, open–loop/closed–loop control is too high (P1466)
–12 Speed range too low (P1466 or P1160 too high)
–13 Ramp–function generator enable missing
–14 Open–loop torque controlled mode is selected
–15 Motor data optimization for the listed motor not permissible (from SW 3.3)
–16 Excessively high current results in limiting by the i2t power module model
Diagnostic parameters are display parameters, i.e. they can only be
read.
The following parameters are used for diagnostics:
Table 4-3 Diagnostic parameters
Parameters
No. Name Min. Standard Max. Units Effective
0599 Active motor data set (from SW 2.4) – – – hex RO
... indicates whether the motor changeover has been enabled, or which motor data set is active.
0 Motor changeover inhibited (P1013 = 0)
1 Motor data set 1 (P1xxx) active
2 Motor data set 2 (P2xxx) active
3 Motor data set 3 (P3xxx) active
4 Motor data set 4 (P4xxx) active
Note:
Motor changeover is described in Chapter 6.11.
Diagnostic
parameters
04.99