4
01.99
4.5 Function–initiating and diagnostic parameters
4-135
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 4-3 Diagnostic parameters, continued
Parameters
No. EffectiveUnitsMax.StandardMin.Name
0600 Operating display hex RO
... displays the actual operating status of the unit.
Traversing to fixed endstop
Motor type
Equipment status
Central enable (terminal 63
or 48) missing
or a fault is present
Operating mode
Drive not
enabled
Parameter set 0 ... 7
Synchr. motor,
standard
Induction mot.,
standard
Induction motor
no encoder,
open–loop contr.
Induction motor,
no encoder,
closed–loop contr.
Synchronous motor,
field–weakening
operation
Closed–loop speed
controlled operation
Open–loop
torque controlled
operation
Module–specific, pulse
enable (terminal 633) missing
Controller enable
(terminal 64 or 65.x)
missing
Ramp–function generator
enable missing
All enable signals present,
motoring
All enable signals present,
generating
O1.x: Ramp–up completed
O2.x: | n
act
| < n
min
O0.x: Ready or no fault
O3.x: Motor temperature pre–warning
Freely parameterizable output terminals (standard assignment for n–set)
V/Hz operation
Positioning mode
Setpoint enable missing
(STW1.6)
Power–on inhibit present
Inverter enable missing
(STW1.3)
ON/OFF 1 missing (STW1.0)
Enable/OFF 2 missing
(STW1.1)
Operating condition/OFF 3
missing (STW1.2) or no control
requested (STW1.10)
Point lit
––> PROFIBUS
has
the master function
Point flashes
––>
clock–synchronous
operation active
Drive is inactive or
the parking axis has been selected
Override is zero
Jogging 1/2
Tracking
operation
Reference point still
not approached
Referencing running
Reject traversing
task
Intermediate
stop
Activate
traversing task
(edge)
Trav. block
running
Parameterized
speed setpoint source
F: Fixed setpoint
A: Analog
O: Digital
n–set
operating mode
pos
Point is lit ––> wait for the signal edge, ”motor
changed over” (STW2.11)
Synchronous
motor, linear
Permanent
coupling
Point lit
––> wait for
an external block
change
MDI active
4 Commissioning