6
6.2 Positioning mode (P0700 = 3, from SW 2.1)
6-375
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Using the position–dependent switching signals 1 and 2, cams can be
simulated without any mechanical equipment (e.g. at inaccessible posi-
tions), dependent on the actual position value.
The absolute cam switching positions are entered via parameter, and
the associated cam switching signals are output as output signal.
Notice
Only after the axis has been referenced, is it guaranteed that the cam
switching signals really do have a ”true” position reference when
output.
This means that an AND logic operation must be externally established
between the ”Reference point set/reference point not set” output signal
and the ”Cam switching signals 1, 2” output signals (e.g. using an
external PLC).
Table 6-22 Parameters for position–related switching signals (cams)
No.
Name Min. Standard Max. Units Effective
0310 Cam switching position 1 –200 000 000 0 200 000 000 MSR Immedi-
ately
0311 Cam switching position 2 –200 000 000 0 200 000 000 MSR Immedi-
ately
The cam switching positions 1 and 2 are set using these parameters.
The following assignment applies:
P0310 (cam switching position 1) ––> cam switching signal 1
P0311 (cam switching position 2) ––> cam switching signal 2
Note:
Also refer under the index entry ”Output signal, cam switching signals 1 and 2”
Position–related
switch signals
(cams)
P0310
P0311
6 Description of the Functions
01.99
! not 611ue !
06.04