6.4 Input/output terminals of the control board
6-508
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 6-49 List of output signals, continued
Operating
mode
Signal name, description PROFIBUS bitposn–setFct. No.
Integrator inhibit, speed controller – x x ZSW2.6
This output signal is used to signal whether the integral component of the speed controller is inhibited or
enabled.
1 signal Integrator inhibit, speed controller
0 signal The speed controller integrator is not inhibited
Parameter set
1st input/2
0
2nd input/2
1
3rd input/2
2
–
–
–
x
x
x
x
x
x
ZSW2.0
ZSW2.1
ZSW2.2
These 3 output signals are used to output the selected parameter set.
Parameter set 0 1 2 3 4 5 6 7
1st input/weighting 2
0
01010101
2nd input/weighting 2
1
00110011
3rd input/weighting 2
2
00001111
Note:
The ”parameter set changeover” function is described in Chapter 6.10.
Motor 1 selected (from SW 2.4)
Motor 2 selected
Motor 3 selected
Motor 4 selected
11
12
13
14
x
x
x
x
–
–
–
–
–
–
–
–
The motor changeover contactors are controlled via these output terminal signals.
1 signal Motor 1, 2, 3 or 4 is selected
0 signal The motor has not been selected
Note:
The motor changeover version and therefore the behavior of the terminal, is selected using P1013
(motor changeover).
To select the motors or motor data sets, input terminal signals are available with function numbers 5
and 6 (motor data set changeover 1st input/2nd input).
Motor changeover is described in Chapter 6.11.
6 Description of the Functions
08.0102.02