6.4 Input/output terminals of the control board
6-509
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 6-49 List of output signals, continued
Operating
mode
Signal name, description PROFIBUS bitposn–setFct. No.
Status, fixed speed setpoint (from SW 3.1)
1st output/2
0
2nd output/2
1
3rd output/2
2
4th output/2
3
15
16
17
18
x
x
x
x
–
–
–
–
–
–
–
–
These output signals are used to display which fixed setpoint is selected via the input signals, and which
parameters specify the speed setpoint.
Fixed speed setpoint 1 2 3 4 5 ... 15
1st output/weighting 2
0
010101...1
2nd output/weighting 2
1
001100...1
3rd output/weighting 2
2
000011...1
4th output/weighting 2
3
000000...1
Effective –
fixed speed setpoint P0641:1
P0641:2
P0641:3 to P0641:15
Note:
The ”fixed speed setpoint” function is described in Chapter 6.1.6.
Refer to the ”Fixed speed setpoint 1st to 4th input” output signal in Chapter 6.4.3.
x – ZSW1.8
set
act
x x MeldW.8
This output signal is used to display whether the speed actual value (n
act
) has entered the tolerance
bandwidth (P1426), and has remained in this tolerance bandwidth for at least a time (P1427).
1 signal
0 signal
n
set
t
1 signal
0 signal
Ramp–up completed
n
act
n
set
= n
act
P1427
Tolerance band
P1426
Note:
When spindle positioning is selected (P0125=1), ZSW1.8 behaves/responds just the same as
Fct. No. 58 (positioning mode)
6 Description of the Functions