6.10 Parameter set changeover
6-578
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 6-59 Parameter set–dependent parameters, continued
Parameters for parameter set Operating
mode
0 Descriptionposn
set
7...1
1417:0 1417:1 ... 1417:7 x x n_x for ”n_act < n_x” signal
1418:0 1418:1 ... 1418:7 x x n_min for ”n_act < n_min” signal
1421:0 1421:1 ... 1421:7 x x Time constant, integrator feedback (speed controller)
1426:0 1426:1 ... 1426:7 x x Tolerance bandwidth for ”n_set = n_act” signal
1428:0 1428:1 ... 1428:7 x x Threshold torque M_x (ARM, SRM)
Threshold force F_x (SLM)
1451:0 1451:1 ... 1451:7 x x P gain, speed controller IM (ARM)
1453:0 1453:1 ... 1453:7 x x Integral action time, speed controller IM (ARM)
1500:0 1500:1 ... 1500:7
Speed setpoint filter (ARM, SRM)
to to to x x
Speed setpoint filter (ARM, SRM)
Velocity setpoint filter (SLM)
1521:0 1521:1 ... 1521:7
Velocity setpoint filter (SLM)
Note:
x: The parameter is available in this operating mode
–: The parameter is not available in this operating mode
x
1)
for spindle positioning (from SW 5.1)
Note
Only parameter set 0 is parameterized using this SimoCom U
parameterizing and start–up tool via the interactive dialog operation.
Parameter sets 1 to 7 must be parameterized using the Expert list of
SimoCom U.
You can toggle between parameter sets 0 and 7 using
the following input signals:
Input signal ”parameter set changeover 1st input”
Input signal ”parameter set changeover 2nd input”
Input signal ”parameter set changeover 3rd input”
How can you
toggle between
parameter sets?
6 Description of the Functions
04.9902.02