7
7.3 List of faults and warnings
7-678
 Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
708 Axial deviations in current controller cycle
Cause On a 2-axis module, the current controller cycle is different for both
axes.
Remedy Check P1000 and set the input values the same for both drives.
Acknowledgement POWER ON
Stop response STOP II (SRM, SLM) STOP I (ARM)
709 Axial deviations in speed controller cycle
Cause On a 2-axis module, the speed controller cycle is different for both
axes.
Remedy Check P1001 and set the input values the same for both drives.
Acknowledgement POWER ON
Stop response STOP II (SRM, SLM) STOP I (ARM)
710 Axial deviations in position controller or interpolation
cycle
Cause For a 2-axis module, the position controller clock cycle (P1009) or the
interpolation clock cycle (P1010) is different for the two axes.
Remedy Check P1009/P1010 and set the input values for both drives the same.
Acknowledgement POWER ON
Stop response STOP II (SRM, SLM) STOP I (ARM)
716 Invalid torque constant
Cause The ratio between the rated torque and rated current (torque constant
[Nm/A]) in P1113 is incorrect (less than/equal to zero) or the ratio
P1113/P1112 is greater than 70.
Remedy Enter the valid torque/current ratio for the motor used in P1113 or enter
a permissible ratio of P1113/P1112.
Third-party motor:
The torque constant should be determined from the motor data sheet.
Siemens motor:
The torque constant is defined by the motor code (P1102).
Acknowledgement POWER ON
Stop response STOP II (SRM, SLM) STOP I (ARM)
7 Fault Handling/Diagnostics
01.99
04.05