7.3 List of faults and warnings
7-709
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
875 Axial deviations in fixed voltage
Cause For the axes of a drive module, an unequal fixed voltage (P1161) has
been set.
As a fixed voltage <> 0 replaces the DC link voltage measured value,
but the DC link voltage is only measured once for all drives of a drive
module, the fixed voltage on all module axes must be equal, before it is
accepted.
Remedy Set the same fixed voltage (P1161) on all module axes.
Acknowledgement not required
Stop response STOP VII
876 Terminal function \%u in the actual mode illegal
Cause The function number, used as input terminal or distributed input
(P0888) may not be used in the actual mode.
Remedy Change P0700 (operating mode) or enter a suitable function number in
P0888 or P0660, P0661 etc.
Acknowledgement not required
Stop response STOP VII
877 Output function \%u not permissible in the actual oper-
ating mode
Cause The function number, used as output, may not be used in the actual
operating mode.
Remedy Change P0700 (operating mode) or enter a suitable function number in
P0680, P06981, etc.
Acknowledgement not required
Stop response STOP VII
878 Input I0.x not parameterized as equivalent zero mark
Cause When entering an external signal as equivalent zero mark (P0174 = 2),
input I0.x must be assigned ”equivalent zero mark” function (Fct.
No.:79).
if a direct measuring system is used, input I0.B must be assigned the
”equivalent zero mark” function (Fct. No.: 79).
Remedy – Motor measuring system: P0660 = 79
– Direct measuring system: P0672 = 79
Acknowledgement not required
Stop response STOP VII