879 Time constant deadtime, speed feedforward control
(P0205:\%u) too high
Cause P0205:8 may not be greater than two position controller clock cycles.
Higher values are internally limited.
Remedy Reduce P0205:8 to max. two position controller clock cycles (P1009).
Parameterize an addition delay via P0206:8.
Acknowledgement not required
Stop response STOP VII
881 PZD configuring: Signal number in P0915:\%u invalid
Cause An undefined or illegal signal number in the current operating mode
(P0700) was identified for the process data software.
The process data for encoder 1 has been configured although encoder-
less operation is activated (P1011.5).
The process data for encoder 2 were configured although the direct
measuring system is not activated (P0879.12).
Remedy Correct P0915:17
Acknowledgement not required
Stop response STOP VII
882 PZD configuring: Double word signal number in
P0915:\%u invalid
Cause For signals with double words (length = 32 bits), the corresponding sig-
nal identifier must be configured twice for adjacent process data. The
following subparameter must therefore also be parameterized with the
same signal number.
Remedy Correct P0915:17
Acknowledgement not required
Stop response STOP VII
883 PZD configuring: Signal number in P0916:\%u invalid
Cause An undefined or illegal signal number in the current operating mode
(P0700) was identified for the process data software.
The process data for encoder 1 has been configured although encoder-
less operation is activated (P1011.5).
The process data for encoder 2 were configured although the direct
measuring system is not activated (P0879.12).
Remedy Correct P0916:17
Acknowledgement not required
Stop response STOP VII