A.1 Parameter list
A-756
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
0607 Analog setpoint term. 56.x/14.x
Min Standard Max Unit Data type Effective
0 1 2 – Unsigned16 immed.
... defines whether and how the analog setpoint is used at this analog input.
0off
1 n-set/M-set operation (speed or torque setpoint interface, refer to Note)
2 Override (position setpoint interface and positioning)
Note:
It is always possible to toggle between n-set/M-set operation using the ”Open-loop torque-con-
trolled operation” input signal.
Analog setpoint for n-set/M-set ––> refer to the index entry ”Analog inputs”
Analog setpoint for velocity override ––> refer to the index entry ”Override”
0608 Inversion term. 56.x/14.x
Min Standard Max Unit Data type Effective
0 0 1 – Unsigned16 immed.
An inversion inverts the polarity of the analog setpoint at this terminal internally.
1 Inverted
0 Not inverted
0609 Smoothing time, terminal 56.x/14.x
Min Standard Max Unit Data type Effective
0.0 3.0 1000.0 ms Floating Point immed. (ARM)
0.0 0.0 1000.0 ms Floating Point immed. (SRM SLM)
This allows the output value of the A/D converter to be smoothed using a PT1 filter.
0610 Drift/offset correction term. 56.x/14.x
Min Standard Max Unit Data type Effective
–9999.9 0.0 9999.9 mV(pk) Floating Point immed.
If the motor erroneously rotates when a speed setpoint of 0 V is entered, a voltage offset can
be applied to set the analog input to zero using this parameter.
0611 Voltage at term. 24.x/20.x
Min Standard Max Unit Data type Effective
– – – V(pk) Floating Point RO
... displays the analog voltage presently available at this input terminal.
0612 Analog setpoint term. 24.x/20.x
Min Standard Max Unit Data type Effective
0 0 3 – Unsigned16 immed.
... defines whether and how the analog setpoint is used at this analog input.
0off
1 n-set/M-set operation (refer to Note)
2 M-red operation
3 Equalization controller operation
Note:
It is always possible to toggle between n-set/M-set operation using the ”Open-loop torque con-
trolled mode” input signal.
Analog setpoint for n-set/M-set/M-red ––> refer to the index entry ”Analog inputs”
Analog setpoint for velocity override ––> refer to the index entry ”Override”