A
A.1 Parameter list
A-758
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
0619 Normalization voltage, torque setpoint (ARM SRM)
Normalization voltage, force setpoint (SLM)
Min Standard Max Unit Data type Effective
5.0 10.0 12.5 V(pk) Floating Point immed.
This defines at which input voltage at terminal 56.x/14.x and/or terminal 24.x/20.x for open-loop
torque controlled operation, the normalization of the torque setpoint (P1241:8) is reached.
Example:
SRM: P0619 = 10, P1241:8 = 10 Nm –> at 10 V, the torque is 10 Nm
SLM: P0619 = 10, P1241:8 = 1720 N –> at 10 V, the force is 1720 N
0620 Normalization voltage, torque/power reduction. (ARM SRM)
Normalization voltage, force/power reduction (SLM)
Min Standard Max Unit Data type Effective
5.0 10.0 12.5 V(pk) Floating Point immed.
The parameter defines at which input voltage of terminal 24.x/20.x, the normalization, torque
reduction (P1243:8, motor data set-dependent) is reached.
0623 DAC normalization, actual speed (ARM SRM)
DAC normalization, motor actual velocity (SLM)
Min Standard Max Unit Data type Effective
–200.0 100.0 200.0 % Floating Point immed.
If signal number 34 (actual motor speed, finely normalized) is selected for the analog output,
when the maximum speed is reached, the following voltage is output as a function of parameter
P0623:
P0623 = 100% –> 1.0 * 10 V = +10 V
P0623 = 50% –> 0.5 * 10 V = +5 V
The following is valid for the maximum speed:
Max. permissible actual speed for synchronous motors: Minimum from 1.2 x P1400 and P1147
Max. permissible actual speed for induction motors: Minimum from P1146 and P1147
0624 DAC normalization, motor utilization
Min Standard Max Unit Data type Effective
–200.0 100.0 200.0 % Floating Point immed.
If signal number 35 (utilization, finely-normalized) is selected for the analog output, then when
the motor is utilized to 100%, the following voltage is output dependent on P0624:
P0624 = 100% –> 1.0 * 10 V = +10 V
P0624 = 50% –> 0.5 * 10 V = +5 V
Note:
Motor utilization ––> refer to P0604
0625 DAC normalization, torque setpoint (ARM SRM)
DAC normalization, force setpoint (SLM)
Min Standard Max Unit Data type Effective
–200.0 100.0 200.0 % Floating Point immed.
If the signal number 36 (torque setpoint, finely-normalized) is selected for the analog output,
then at twice the rated torque, the following voltage is output dependent on P0625:
P0625 = 100% –> +10 V
P0625 = 50% –> +5 V
Note: Signal No. 36 is output signed.