5 Operation
5.1 General
Manual
SIPART DR21
C73000-B7476-C143-08
149
5 Operation
5.1 General
D Operating modes
The SIPART DR21 is operated exclusively and fully with the operating keys on the front
module. The function of the operating panel can be switched between three main levels:
Process operation
mode
The process values x, w, y and the controller status are displayed,
the process operation mode can be controlled by the operating keys.
Selection level Here the list is selected which can be changed or activated in the
configuration mode. These are the following lists:
onPA Online parameters
(AdAP) Start adaptation
oFPA Offline parameters
StrS Structure switches
(CAE3) Set UNI-module
APSt all preset
The lists for onPA, oFPA, StrS and APST are always displayed in
the selection mode.
The lists for AdAP and CAE3 only appear in the display when they
have been selected by structure switches.
Configuration
modes
Settings are made in the selected list or functions are activated.
Some of the keys and displays on the front module are assigned different control and display
functions when the operating mode is changed. See the description of the respective main
level for details.
D Operating locks
Operation of the controller or access to the selection or configuration modes can be locked
by digital signals. The following blocking steps are possible:
bLb Blocking, Operation
The complete operation of the controller is blocked. Exception: Switching over the
w/x digital display. bLb” appears in the display on pressing the operating k eys.
bLS Blocking, Structuring
Blocking the lists AdAP, oFPA, StrS, CAE3 and APSt.
Only the list for onPA is accessible. ”bLS” appears in the display when the blocked
mode is called
bLPS Blocking, Parameterization and Structuring
The complete selection and configuration mode is blocked. The process operation
mode is free. bLPS” appears in the display when the blocked mode is called