5 Operation
5.4 Configuration modes
Manual
SIPART DR21
C73000-B7476-C143-08
175
5.4.6.1 Measuring range for mV (S8 = 0)
D MA/ME – set measuring range
Call parameters MA, ME, set range start and full scale:
Measuring range limits -175 mV ≤MA ≤ME ≤+175 mV
D CA/CE – fine adjustment (only if necessary)
Call parameter CA,
Set signal to start of scale
Correct the display with CA if necessary
Call parameter CE,
Set signal to full scale,
Correct the display with CE if necessary
5.4.6.2 Measuring range for U, I (S8 = 0)
only with measuring range plug 6DR2805-8J
D MA/ME – set measuring range
Call parameters MA, ME, set range start and full scale:
Measuring range limits -175 mV ≤MA ≤ME ≤+175 mV
Initialization in the measuring range plug
0 to 10V or 0 to 20mA signal corresponds to MA = 0mV ME = 100mV
2 to 10V or 4 to 20mA signal corresponds to MA = 20mV ME = 100mV
D CA/CE – fine adjustment (only if necessary)
Call parameter CA,
Set signal to start of scale
Correct the display with CA if necessary
Call parameter CE,
Set signal to full scale,
Correct the display with CE if necessary
5.4.6.3 Measuring range for thermocouple with internal reference point (S8 = 1)
D MA/ME – set measuring range
Call parameters MA, ME, set the start of scale and full scale according to the thermocouple
type (S9) and the temperature unit (S10).