5 Operation
5.4 Configuration modes
Manual
164
SIPART DR21
C73000-B7476-C143-08
oFPA Offline parameter list
ydisplay w/xdisplay
Parameter
Param-
names
Min. Max.
Factory
setting
Unit
Decimal point w/x num. dP _.-- -- -- -- -- -- -- ___.-- --
Startofscale dA --1999 9999 0.0
Full scale dE --1999 9999 100.0
Alarm 1 A1 --110% to 110% 5.0
Alarm 2 (A2≤A1) A2 from dA, dE --5 . 0
Alarm 3 A3 at S76 / S77 = 5.0
Alarm 4 (A4≤A3) A4 0 to 5 and 17 --5 . 0
Hysteresis alarms HA 0.1 10.0 1.0 %
Setpoint start SA --10% to 1 10% --5. 0
Setpoint end SE from dA, dE 105.0
Safety setpoint SH 0.0
Setpoint ramp time tS oFF/0.100 9984 oFF min
Ratio factor start vA 0.000 9.999 0.000 1
Ratio factor end vE 0.000 9.999 1.000 1
Safety output variable YS --10.0 110.0 0.0 %
Split range left (Y1≤Y2) Y1 0.0 100.0 50.0 %
Split range right Y2 0.0 100.0 50.0 %
L--1 --10.0 110.0 --10.0 %(1)
L0 --10.0 110.0 0.0 %(1)
L1 --10.0 110.0 10.0 %(1)
.
L8 --10.0 110.0 80.0 %(1)
L9 --10.0 110.0 90.0 %(1)
L10 --10.0 110.0 100.0 %(1)
L11 --10.0 110.0 110.0 %(1)
Decimal point
1)
Pd _. -- -- -- ____ ___.--
Start value
1)
Ad --1999 9999 0.0 --
Full scale value
1)
Ed --1999 9999 100.0
1)
as of software version -A9, only in ratio controller (S1 = 3)
Display range of controlled variable x1 and the weighted commanding process variable w (S81 = 7)
Table 5-4 Offline parameter list