5 Operation
5.4 Configuration modes
Manual
SIPART DR21
C73000-B7476-C143-08
159
Process op-
eration mode
BLB = 0, BLPS = 0
Shift key
press for about 5 s
Selection
mode
onPA
AdAP
Configuration level AdAP
Pre-adaptation
Pre-settings
Adaptation LED (19) off
(6)
Exit
(16)
Enter
(11)
Exit
(16)
Δw-
keys
(14, (15)
During adaptation
Adaptation LED (19) flashing
Complete process display
Parameter select-
able with Δykeys
(7), (8)
2)
Parameter set
selectable with
Δw keys (14),
(15)
Start of
adaptation
Enter key
(11)
1)
xx = manipulated variable
old para-
meter-
values
remain
retained
Enter
(11)
Error
message
acknowledge
Adaptation
repeat
Aborted adaptation
Adaptation LED (19) off
by errors
in the adap-
tation me-
thod see ta-
ble 5-3,
page 162
manually
by
Exit key
Error message
Exit AdAP for
error c orrection
Switch controller
to automatic
mode, new pa-
rameters are
effective
Old parameters
are overwritten
by new parame-
ters
Switch controller
to manual mode,
set desired
operating point
and wait for
stationary condi-
tion.
tU 0FF,0.1to24h
dPv nEG, PoS
dY 0,5to90%
xx
1)
Strt
w
cP
tn
tv
AH
xx
1)
Strt
Old values can
only be set in
onPA configur-
ation level
Post adaptation
Adaptation LED (19) on
vv
cP
tn
tv
AH
new para-
meter values
can be chan-
ged with Δw
keys (14),
(15)
Pi..x
Pid.x
2)
new parameter
values are provided for transfer
Figure 5-4 Overview configuration level AdAP