EasyManuals Logo

Siemens SIPART DR21 User Manual

Siemens SIPART DR21
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #172 background imageLoading...
Page #172 background image
5 Operation
5.4 Configuration modes
Manual
172
SIPART DR21
C73000-B7476-C143-08
Structure
switch
switch
posi-
tion
Function
S84 Serial interface (slot 4)
0 without
[1] with serial interface, with lock via RC
2
1)
with serial interface, with lock via CB
3
1)
with serial interface, without lock
1)
as of software version --C1
S85 Data transfer
0
[1]
2
3
4
5
Reception Control signal Source for
by DR21 CB
DI
/CB
ES
w
E
y
N
nothing only w
EA yN
Configuring CB
DI
Configuring CB
DI
CB
ES
w
ES
y
ES
Process var. CB
DI
CB
ES
Status register CB
DI
CB
ES
w
EA
y
N
CB
DI
CB
ES
S86 Data transfer rate
[0}
1
9600 bps
4800 bps
2 2400 bps
3 1200 bps
4 600 bps
c
e
5 300 bps
e
rfac
e
S87 Cross parity
inte
[0] even
rial i
1 odd
Ser
i
S88 Longitudinal parity position
[0] without
1 after ETX
2 before ETX
S89 Longitudinal parity
[0] normal
1 inverted
S90 Station number
[0] 0
to to
125 125
S91 Time monitoring CB (ES)
[0] without time monitoring
1to 1sto
25 25 s
S92 see structure switch S33 following
Table 5-5 Structure switches

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART DR21 and is the answer not in the manual?

Siemens SIPART DR21 Specifications

General IconGeneral
BrandSiemens
ModelSIPART DR21
CategoryController
LanguageEnglish

Related product manuals