Addr. Parameter Function C Setting Options Default Setting Comments
7248 bef.1.Cy:50-3 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50-3
7249 bef.1.Cy:50N-3 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50N-3
7250 bef.2.Cy:50-3 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 50-3
7251 bef.2.Cy:50N-3 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 50N-3
7252 bef.3.Cy:50-3 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 50-3
7253 bef.3.Cy:50N-3 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 50N-3
7254 bef.4.Cy:50-3 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 50-3
7255 bef.4.Cy:50N-3 79M Auto Recl. Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 50N-3
8101 MEASURE. SUPERV Meas-
urem.Superv
OFF
ON
ON Measurement Supervision
8104 BALANCE I LIMIT Meas-
urem.Superv
1A 0.10 .. 1.00 A 0.50 A Current Threshold for
Balance Monitoring
5A 0.50 .. 5.00 A 2.50 A
8105 BAL. FACTOR I Meas-
urem.Superv
0.10 .. 0.90 0.50 Balance Factor for Current
Monitor
8106 Σ I THRESHOLD Meas-
urem.Superv
1A 0.05 .. 2.00 A; ∞ 0.10 A Summated Current Moni-
toring Threshold
5A 0.25 .. 10.00 A; ∞ 0.50 A
8107 Σ I FACTOR Meas-
urem.Superv
0.00 .. 0.95 0.10 Summated Current Moni-
toring Factor
8109 FAST Σ i MONIT Meas-
urem.Superv
OFF
ON
ON Fast Summated Current
Monitoring
8110A T BAL. V LIMIT Meas-
urem.Superv
0 .. 100 sec 5 sec T Balance Factor for
Voltage Monitor
8111A T BAL. I LIMIT Meas-
urem.Superv
0 .. 100 sec 5 sec T Current Balance
Monitor
8201 FCT 74TC 74TC TripCirc. ON
OFF
ON 74TC TRIP Circuit Supervi-
sion
8202 Alarm Delay 74TC TripCirc. 1 .. 30 sec 2 sec Delay Time for alarm
Functions, Settings, Information
F.2 Settings
400 SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016