EasyManua.ls Logo

Siemens SIPROTEC 4 7SJ61 - Page 401

Siemens SIPROTEC 4 7SJ61
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Addr. Parameter Function C Setting Options Default Setting Comments
8301 DMD Interval Demand meter 15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min.,10 Subs
5 Min., 5 Subs
60 Min., 1 Sub Demand Calculation Inter-
vals
8302 DMD Sync.Time Demand meter On The Hour
15 After Hour
30 After Hour
45 After Hour
On The Hour Demand Synchronization
Time
8311 MinMax cycRESET Min/Max meter NO
YES
YES Automatic Cyclic Reset
Function
8312 MiMa RESET TIME Min/Max meter 0 .. 1439 min 0 min MinMax Reset Timer
8313 MiMa RESETCYCLE Min/Max meter 1 .. 365 Days 7 Days MinMax Reset Cycle
Period
8314 MinMaxRES.START Min/Max meter 1 .. 365 Days 1 Days MinMax Start Reset Cycle
in
8315 MeterResolution Energy Standard
Factor 10
Factor 100
Standard Meter resolution
9011A RTD 1 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Pt 100 Ω RTD 1: Type
9012A RTD 1 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Oil RTD 1: Location
9013 RTD 1 STAGE 1 RTD-Box -50 .. 250 °C; ∞ 100 °C RTD 1: Temperature Stage
1 Pickup
9014 RTD 1 STAGE 1 RTD-Box -58 .. 482 °F; ∞ 212 °F RTD 1: Temperature Stage
1 Pickup
9015 RTD 1 STAGE 2 RTD-Box -50 .. 250 °C; ∞ 120 °C RTD 1: Temperature Stage
2 Pickup
9016 RTD 1 STAGE 2 RTD-Box -58 .. 482 °F; ∞ 248 °F RTD 1: Temperature Stage
2 Pickup
9021A RTD 2 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 2: Type
9022A RTD 2 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 2: Location
9023 RTD 2 STAGE 1 RTD-Box -50 .. 250 °C; ∞ 100 °C RTD 2: Temperature Stage
1 Pickup
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7SJ61, Manual 401
C53000-G1140-C210-6, Edition 05.2016

Table of Contents

Related product manuals