Addr. Parameter Function C Setting Options Default Setting Comments
9024 RTD 2 STAGE 1 RTD-Box -58 .. 482 °F; ∞ 212 °F RTD 2: Temperature Stage
1 Pickup
9025 RTD 2 STAGE 2 RTD-Box -50 .. 250 °C; ∞ 120 °C RTD 2: Temperature Stage
2 Pickup
9026 RTD 2 STAGE 2 RTD-Box -58 .. 482 °F; ∞ 248 °F RTD 2: Temperature Stage
2 Pickup
9031A RTD 3 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 3: Type
9032A RTD 3 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 3: Location
9033 RTD 3 STAGE 1 RTD-Box -50 .. 250 °C; ∞ 100 °C RTD 3: Temperature Stage
1 Pickup
9034 RTD 3 STAGE 1 RTD-Box -58 .. 482 °F; ∞ 212 °F RTD 3: Temperature Stage
1 Pickup
9035 RTD 3 STAGE 2 RTD-Box -50 .. 250 °C; ∞ 120 °C RTD 3: Temperature Stage
2 Pickup
9036 RTD 3 STAGE 2 RTD-Box -58 .. 482 °F; ∞ 248 °F RTD 3: Temperature Stage
2 Pickup
9041A RTD 4 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 4: Type
9042A RTD 4 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 4: Location
9043 RTD 4 STAGE 1 RTD-Box -50 .. 250 °C; ∞ 100 °C RTD 4: Temperature Stage
1 Pickup
9044 RTD 4 STAGE 1 RTD-Box -58 .. 482 °F; ∞ 212 °F RTD 4: Temperature Stage
1 Pickup
9045 RTD 4 STAGE 2 RTD-Box -50 .. 250 °C; ∞ 120 °C RTD 4: Temperature Stage
2 Pickup
9046 RTD 4 STAGE 2 RTD-Box -58 .. 482 °F; ∞ 248 °F RTD 4: Temperature Stage
2 Pickup
9051A RTD 5 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 5: Type
9052A RTD 5 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 5: Location
Functions, Settings, Information
F.2 Settings
402 SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016