2 Functions
156
7UM61 Manual
C53000-G1176-C127-3
2.25.4 Information List
6608 KÏ„ at STOP 1.0 .. 100.0 5.0 Extension of Time Constant at
Stop
6609 KÏ„ at RUNNING 1.0 .. 100.0 2.0 Extension of Time Constant at
Running
6610 T MIN. INHIBIT 0.2 .. 120.0 min 6.0 min Minimum Restart Inhibit Time
No. Information Type of In-
formation
Comments
4822 >BLK Re. Inhib. EM >BLOCK Restart inhibit motor
4823 >Emer. Start ΘR EM >Emergency start rotor
4824 Re. Inhibit OFF AM Restart inhibit motor is switched OFF
4825 Re. Inhibit BLK AM Restart inhibit motor is BLOCKED
4826 Re. Inhibit ACT AM Restart inhibit motor is ACTIVE
4827 Re. Inhib. TRIP AM Restart inhibit motor TRIP
4828 >RM th.rep. ΘR EM >Reset thermal memory rotor
4829 RM th.rep. ΘR AM Reset thermal memory rotor
4830 Re. Inhib.ALARM AM Alarm restart inhibit motor
Addr. Parameter Setting Options Default Setting Comments