A.5 Protocol-dependent Functions
377
7UM61 Manual
C53000-G1176-C127-3
A.5 Protocol-dependent Functions
Protocol → IEC 60870–5–
103
Profibus FMS
(on request)
Profibus DP DNP3.0 Modbus
ASCII/RTU
Additional
Service Inter-
face (optional)
Function ↓
Operational
measured
values
Yes Yes Yes Yes Yes Yes
Metered values Yes Yes Yes Yes Yes Yes
Fault Recording Yes Yes No. Only via ad-
ditional service
interface
No. Only via ad-
ditional service
interface
No. Only via ad-
ditional service
interface
Yes
Remote protec-
tion setting
No. Only via ad-
ditional service
interface
Yes No. Only via ad-
ditional service
interface
No. Only via ad-
ditional service
interface
No. Only via ad-
ditional service
interface
Yes
User-defined in-
dications and
switching
objects
Yes Yes Pre-defined
"User-defined
message" in
CFC
Pre-defined
"User-defined
message" in
CFC
Pre-defined
"User-defined
message" in
CFC
Yes
Time synchroni-
zation
Via protocol;
DCF77/IRIG B;
Interface;
Binary input
Via protocol;
DCF77/IRIG B;
Interface;
Binary input
Via
DCF77/IRIG B;
Interface;
Binary input
Via protocol;
DCF77/IRIG B;
Interface;
Binary input
Via protocol;
DCF77/IRIG B;
Interface; Binary
input Protocol
—
Messages with
time stamp
Yes Yes No Ye s No Yes
Commissioning tools
Measured value
indication block-
ing
Yes Yes No No No Yes
Test Mode Yes Yes No No No Yes
Physical mode Asynchronous Asynchronous Asynchronous Asynchronous Asynchronous —
Transmission
Mode
Cyclically/Event Cyclically/Event Cyclically Cyclically/Event Cyclically —
Baud rate 4800 to 38400 Up to 1.5
MBaud
Up to 1.5
MBaud
4800 to 19200 2400 to 19200 2400 to 38400
Type RS 232 RS 485
Fibre Optic
Cable
RS 485 Fibre
Optic Cable:
Single Ring,
Double Ring
RS 485 Fibre
Optic Cable:
Double ring
RS 485 Fibre
Optic Cable
RS 485 Fibre
Optic Cable
RS 232 RS 485
Fibre Optic
Cable
www . ElectricalPartManuals . com