2.10.4 Information List
1706 I2>> 10 .. 100 % 60 % I2>> Pickup
1707 T I2>> 0.00 .. 60.00 sec; ∞ 3.00 sec T I2>> Time Delay
No. Information Type of In-
formation
Comments
5143 >BLOCK I2 EM >BLOCK I2 (Unbalance Load)
5146 >RM th.rep. I2 EM >Reset memory for thermal replica I2
5151 I2 OFF AM I2 switched OFF
5152 I2 BLOCKED AM I2 is BLOCKED
5153 I2 ACTIVE AM I2 is ACTIVE
5156 I2> Warn AM Unbalanced load: Current warning stage
5158 RM th.rep. I2 AM Reset memory of thermal replica I2
5159 I2>> picked up AM I2>> picked up
5160 I2>> TRIP AM Unbalanced load: TRIP of current stage
5161 I2 Θ TRIP AM Unbalanced load: TRIP of thermal stage
5165 I2> picked up AM I2> picked up
Addr. Parameter Setting Options Default Setting Comments