Device Functions
SIRIUS 3RW44 manual
6-8 GWA 4NEB 535 2195-02 DS 06
Typical applications for breakaway pulses
Typical applications for breakaway pulses are load machines with inverse torque
behavior, e.g. crushers and mills.
Note
A breakaway pulse that is set too high may lead to the error message "Current
measurement range exceeded".
Remedy: Use larger starter dimensions or a lower breakaway voltage.
Only set the breakaway pulse when it is really required (e.g. for mills and
crushers).
A wrongly set breakaway pulse, e.g. for pumps, may lead to the error message
"Incorrect start conditions".