PROFIBUS DP Communication Module
SIRIUS 3RW44 manual
8-32 GWA 4NEB 535 2195-02 DS 06
8.9.8 Module Status
Definition
The module status reflects the status of the configured module (here: soft
starter) and represents a specification of the code-based diagnosis. The module
status starts after the code-based diagnosis and comprises 5 bytes.
Module status structure
The structure of the module status is as follows:
Figure 8-6: Structure of the module status
0 0 0 0 0 1 0 1
765 0
Byte 8
Bit number
= 0x05
Length of the module status
including byte 8 (=5 bytes)
Code for module status
0 0 x
765
Byte 12
Bit number
70
Byte 9
82
H
70
Byte 10
0
H
Byte 11
0
H
4
0
3210
Not relevant
Not relevant
00
B
: Soft starter OK; valid user data
01
B
: Soft starter error; invalid user data