Siemens SIRIUS 3RW44 - Data Set 96 - Reading the Maximum Pointer

Siemens SIRIUS 3RW44
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PROFIBUS DP Communication Module
SIRIUS 3RW44 manual
8-58 GWA 4NEB 535 2195-02 DS 06
8.12.13 Data Set 96 - Reading the Maximum Pointer
ID
No.
Byte
Bit
Meaning Value range / [coding]
Incre-
ment
Comment
Maximum pointer
656 4 Phase current I
L1 min
(%) 0 ... 797 % / [0 ... 255] 3.125 % In bypass operation
657 5 Phase current I
L2 min
(%) 0 ... 797 % / [0 ... 255] 3.125 % In bypass operation
658 6 Phase current I
L3 min
(%) 0 ... 797 % / [0 ... 255] 3.125 % In bypass operation
7 Reserved = 0
653 8 Phase current I
L1 max
(%) 0 ... 797 % / [0 ... 255] 3.125 % In bypass operation
654 9 Phase current I
L2 max
(%) 0 ... 797 % / [0 ... 255] 3.125 % In bypass operation
655 10 Phase current I
L3 max
(%) 0 ... 797 % / [0 ... 255] 3.125 % In bypass operation
11 Reserved = 0
652 12 Maximum
tripping current I
A max
(%)
0 ... 1,000 % /
[0 ... 320]
3.125 % Current during switch-off due
to error
651 14 Number of motor overload
trips
0 ... 65,535 /
[0 ... 65,535]
1 Motor protection, temperature
sensor, stalling
659 16 Maximum
tripping current I
A max
(rms)
0 ... 20,000 A /
[0 ... 2,000,000]
0.01 A Current during switch-off due
to error
660 20 Phase current I
L1 min
(rms) 0 ... 20,000 A /
[0 ... 2,000,000]
0.01 A In bypass operation
661 24 Phase current I
L2 min
(rms) 0 ... 20,000 A /
[0 ... 2,000,000]
0.01 A In bypass operation
662 28 Phase current I
L3 min
(rms) 0 ... 20,000 A /
[0 ... 2,000,000]
0.01 A In bypass operation
663 32 Phase current I
L1 max
(rms) 0 ... 20,000 A /
[0 ... 2,000,000]
0.01 A In bypass operation
664 36 Phase current I
L2 max
(rms) 0 ... 20,000 A /
[0 ... 2,000,000]
0.01 A In bypass operation
665 40 Phase current I
L3 max
(rms) 0 ... 20,000 A /
[0 ... 2,000,000]
0.01 A In bypass operation
666 44 Phase-to-phase voltage
U
L1 - L2min
(rms)
0 ... 1,500 V /
[0 ... 15,000]
0.1 V
Reset to 0 after loss of phase
or switch-off of the main
voltage.
667 46 Phase-to-phase voltage
U
L2 - L3min
(rms)
0 ... 1,500 V /
[0 ... 15,000]
0.1 V
668 48 Phase-to-phase voltage
U
L3 - L1min
(rms)
0 ... 1,500 V /
[0 ... 15,000]
0.1 V
669 50 Phase-to-phase voltage
U
L1 - L2max
(rms)
0 ... 1,500 V /
[0 ... 15,000]
0.1 V
670 52 Phase-to-phase voltage
U
L2 - L3max
(rms)
0 ... 1,500 V /
[0 ... 15,000]
0.1 V
671 54 Phase-to-phase voltage
U
L3 - L1max
(rms)
0 ... 1,500 V /
[0 ... 15,000]
0.1 V
672 56 Electronics supply voltage
U
NS min
(rms)
0 ... 1,500 V /
[0 ... 15,000]
0.1 V Reset to zero during "Power
on".