PROFIBUS DP Communication Module
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06
8-59
Table 8-29: Data set 96 - reading the maximum pointer
673 58 Electronics supply voltage
U
NS max
(rms)
0 ... 1,500 V /
[0 ... 15,000]
0.1 V
674 60 Maximum heatsink
temperature
1 ... -40 °C / [-
40 ... 127]
C
675 61 Maximum contact block
temperature rise
0 ... 250 % / [0 ... 250] 1 %
676 62 Minimum line frequency 0 ... 100 Hz / [0 ... 200] 0.5 Hz During network failure or
loss of phase = 0
677 63 Maximum line frequency 0 ... 100 Hz / [0 ... 200] 0,5 Hz
678 64 Operating hours - motor
current = 18 ... 49.9 % x l
e
0 ... 2
32
-1 s / [0 ... 2
32
-
1]
1s
679 68 Operating hours - motor
current = 50 ... 89.9 % x l
e
0 ... 2
32
-1 s / [0 ... 2
32
-
1]
1s
680 72 Operating hours - motor
current = 90 ... 119.9 % x l
e
0 ... 2
32
-1 s / [0 ... 2
32
-
1]
1s
681 76 Operating hours - motor
current = 120 ... 1,000 % x l
e
0 ... 2
32
-1 s / [0 ... 2
32
-
1]
1s
682 80 Operating hours - device 0 ... 2
32
-1 s / [0 ... 2
32
-
1]
1s
84 Reserved = 0
85 Reserved = 0
ID
No.
Byte
Bit
Meaning Value range / [coding]
Incre-
ment
Comment
Maximum pointer