PROFIBUS DP Communication Module
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06
8-51
353 6
2
Quick stop active E26,
E24
The motor is switched off due to a quick stop.
The signal bit is deleted when the cause for the switch-
off has been remedied and acknowledged via "Trip
reset".
6
3
Reserved = 0
361 6
4
Trip reset carried out The signal bit is deleted by update or "Trip reset" in
ready state.
362 6
5
Trip reset not possible Cause for the switch-off is still present.
The signal bit is deleted by update (new "Trip reset") or by
"Trip reset" in ready state.
363 6
6
Maximum pointer deleted The signal bit is always deleted after acknowledgement
with "Trip reset".
317 6
7
Electronics supply
voltage too low
The signal bit is deleted automatically when the cause
for the switch-off is remedied.
Communication
303 7
0
Bus error Watchdog function of the DP interface has elapsed.
The signal bit is updated continuously.
356 7
1
CPU/master STOP PLC program no longer processed.
The signal bit is updated continuously.
357 7
2
Automatic operating mode Automatic (PLC-controlled).
The signal bit is updated continuously.
358 7
3
Manual bus operating mode Manual operation via field bus (O&M controlled).
The signal bit is updated continuously.
359 7
4
Manual operation local operating
mode
Manual operation via local device interface
(O&M controlled). The signal bit is updated continuously.
7
5
Reserved = 0
360 7
6
Connection break
in manual operation local operating
mode
The associated communication connection was
interrupted during manual operation. The signal bit is
updated continuously.
355 7
7
Process image error E26
E24
Process image of the outputs contains impermissible bit
combinations. The signal bit is automatically deleted when
the cause for the switch-off is remedied.
Parameter
364 8
0
Parameterization active The signal bit is updated continuously.
365 8
1
Incorrect parameter value E16 The signal bit is always deleted following an
acknowledgement with "Trip reset" or after valid
parameters have been received.
E24 Causes a switch-off during starting.
366 8
2
Parameter changes not permissible
when ON
Parameter change attempted while motor running or
during the affected device function, causing a switch-off.
The signal bit is always deleted following an
acknowledgement with "Trip reset" or after valid
parameters have been received.
368 8
3
Parameterization disable CPU/
master active
The signal bit is updated continuously.
The soft starter ignores the parameters from the PLC.
8
4-7
Reserved = 0
ID
No.
Byte
Bit
Signal bit
E
No.
*)
Meaning/Acknowledgment