Circuit Examples
SIRIUS 3RW44 manual
9-6 GWA 4NEB 535 2195-02 DS 06
9.1.5 3RW44 in an Inside Delta Circuit
Reversed direction of rotation in an inside delta circuit
Main circuit Option 1a:
Control circuit Option 1: Activation via PLC
Main circuit Option 1b:
Notice
Observe the wiring suggestions for the inside delta circuit on the main
circuit page. Faulty connection may cause breakdowns.
1) For permissible main and control voltage values, refer to Technical Data,
pages 10-12 to 10-16.
2) Caution: risk of restart!
The start command (e.g. by the PLC) must be reset before a reset
command is issued, as an automatic restart is executed when a start
command is pending after the reset command is issued. This
particularly applies to motor protection tripping.
For safety reasons, we recommend integrating the group error output
(terminals 95 and 96) into the control.