PROFIBUS DP Communication Module
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06
8-9
8.4 Activating the PROFIBUS DP Communication Module (Field
Bus Interface) and Setting the Station Address
8.4.1 Introduction
Activate the PROFIBUS DP communication module (device function "Field bus")
and set the station address either via the display or via the device interface using
the "Soft Starter ES Premium" or the "Soft Starter ES + SP1" software.
Notice
After the communication module has been activated, the control priority
automatically switches from the inputs to the PROFIBUS DP communication
module.
If an input is active with the "Manual operation local" function, the control priority
does not change (refer to Chapter 5.4.7 "Parameterizing the Inputs" on Page 5-
28).
The station address of the soft starters is pre-set to 126 as the factory default.