8.12.15 Data Sets 131, 141, 151 - Technology Parameters 2: Reading/Writing Set 1, 2, 3
Byte
Bit
Value Comment
Preamble
0 Coordination Writing 0x20 via channel C1 (PLC)
Writing 0x30 via channel C2 (PC)
Writing 0x40 via device interface (PC)
1 - 3 Reserved = 0
ID
No.
Byte
Bit
Meaning
Only for
data set
131
Value range [coding] Factor
120 4 - 7 Device function_2 x
1 8 - 11 Device function_1 x
130 12 Rated operating current I
e
0 ... 2 ,000 A [0 ... 200, 000] 0.01 A
316
0
Load type x 3-phase [0]
416
1
Protection against voltage failure x No [0]
•Yes [1]
16
2-7
Reserved = 0
136 17 Prewarning limit - motor heat build-up x 0 ... 95 % [0 ... 19] 5 %
518
0-2
Response to overload - thermal motor
model
x Tripping without restart [0]
Tripping with restart [1]
Warning [2]
18
3-7
Reserved = 0
619
0-4
Tripping class x CLASS 5 (10a) [3]
CLASS 10 [0]
CLASS 15 [4]
CLASS 20 [1]
CLASS 30 [2]
CLASS OFF [15]
19
5-7
Reserved = 0
7 20 Pre-charge time x 60 ... 1 ,800 s [2 ... 60] 30 s
8 21 Idle time x 0 ... 255 s [0 ... 255] 1 s
137 22-23 Prewarning limit - remaining time for
tripping
x 0 ... 500 s [0 ... 500] 1 s
10 24
0-1
Response to overload - temperature sensor x Tripping without
restart [0]
Tripping with restart [1]
Warning [2]
24
2-3
Reserved = 0
924
4-6
Temperature sensor x Deactivated [0]
Thermo click [1]
PTC - type A [2]