Commissioning
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06
5-11
5.4.2 Entering the Motor Data
Figure 5-6: Entering the motor data and name plate
Rated operating 
current I
e
Notice 
Always set the rated operating current of the motor stated on the motor name plate based 
on the prevailing line voltage. This setting is independent of the type of connection of the 
soft starter (soft starter in standard or inside delta circuit). Value to be set in the above 
example for a line voltage of 400 V, e.g. 40.5 A.
The motor current of the connected drive should be set to ensure proper functioning of the 
soft starter during starting and stopping, as well as in regard to motor protection.