Commissioning
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06
5-11
5.4.2 Entering the Motor Data
Figure 5-6: Entering the motor data and name plate
Rated operating
current I
e
Notice
Always set the rated operating current of the motor stated on the motor name plate based
on the prevailing line voltage. This setting is independent of the type of connection of the
soft starter (soft starter in standard or inside delta circuit). Value to be set in the above
example for a line voltage of 400 V, e.g. 40.5 A.
The motor current of the connected drive should be set to ensure proper functioning of the
soft starter during starting and stopping, as well as in regard to motor protection.
ESC OK
ESC OK
change
Rated operating
speed
3
OK
Function call
1470
Copy motor data
to PS2+3
ESC OK
OK
Copy motor data
to PS2+3
execute?
ESC
ESC OK
change
ESC OK
Motor 1
1
Rated operating
current Ie
1
change
Rated operating
torque
2
40.5 A
143 Nm
Adjustable
from ... to
0 ... I
e
(3RW44 device
name plate)
0 ... 10,000 Nm
500 ... 3,600 min
-1
ESC
Parameter
1
set 1
ESC
Settings
3
OK
Display mea-
select
SIEMENS
Menu
3RW44
1
sured value
ESC
ESC OK
OK
select
1
Status
select
2
display
ESC OK
OK
OK
OK
select
select
select

Table of Contents

Other manuals for Siemens SIRIUS 3RW44

Related product manuals