PROFIBUS DP Communication Module
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06
8-67
8.12.17 Data Set 133 - Technology Parameters 4: O&M Module
Table 8-34: Data set 133 - technology parameters 4: O&M module
Byte
Bit
Value Comment
Preamble
0 Coordination Writing 0x20 via channel C1 (PLC)
Writing 0x30 via channel C2 (PC)
Writing 0x40 via device interface (PC)
1 - 3 Reserved = 0
ID No. Byte
Bit
Meaning Value range [coding] Factor
4 Reserved = 0
179 8
0-3
Language English [0]
German [1]
French [2]
Spanish [3]
Italian [4]
Portuguese [5]
181 8
4-7
Lighting brightness Normal [0]
Off with time delay [4]
•Off [5]
180 9 Contrast display 0 ... 100 % [0 ... 20] 5 %
182 10
0-3
Lighting response to fault Unchanged [0]
•On [1]
Blinking [2]
Flickering [3]
183 10
4-7
Lighting response to warning Unchanged [0]
•On [1]
Blinking [2]
Flickering [3]
11 Reserved = 0
184 12 Reaction time keys 10 ... 100 % [2 ... 20] 5 %
185 13 Auto repeat speed 10 ... 100 % [2 ... 20] 5 %
186 14 Auto repeat time 10 ... 250 ms [2 ... 50] 5 ms
187 15 O&M keys - activity monitoring time 0 ... 1,800 s [0 ... 60] 30 s