Commissioning
SIRIUS 3RW44 manual
5-36 GWA 4NEB 535 2195-02 DS 06
5.4.13 Activating the Field Bus Interface (PROFIBUS DP)
For information on activating the field bus interface, please refer to Chapter 8.4 
"Activating the PROFIBUS DP Communication Module (Field Bus Interface) and 
Setting the Station Address".
Notice 
If the parameter "Parameters disabled CPU/Master" is set to "Off" (factory setting), the 
parameters set on the soft starter will be overwritten with the values stored in the GSD file 
or in the OM when the bus is started. If this is not desired, the parameter must be set to 
"On". 
Fieldbus
select
1
change
interface
On
ESC OK
Group diagnosis
select
2
change
Disable
ESC OK
Response to
3
change
Substitute value
ESC OK
CPU master stop
Baud rate
5
12,000 kBd
Station address
select
4
change
126
Status
select
2
display
select
Settings
select
3
select
Display mea-
select
1
sured value
select
SIEMENS
Menu
3RW44
ESC OK
ESC OK
ESC OK
ESC OK
Parameter
select
1
 
select
set 1
Saving
select
11
 
select
options
Fieldbus
select
10
select
ESC OK
ESC OK
ESC OK
Substitute value
select
6
select
Parameters disabled
select
7
change
Off
ESC OK
ESC OK
CPU/Master
ESC OK
ESC OK