Commissioning
SIRIUS 3RW44 manual
5-26 GWA 4NEB 535 2195-02 DS 06
5.4.5 Setting Slow Speed Parameters
Figure 5-20:Setting slow speed parameters
change
ESC
Slow speed
1
ESC
Slow speed
4
OK
parameters
7
OK
ESC
Slow speed
3
7
OK
ESC
Slow speed
2
80.0 %
OK
ESC
Slow speed
4
80.0 %
OK
torque right
factor right
factor left
torque left
Adjustable
from ... to
3 ... 21
20 ... 100 %
3 ... 21
20 ... 100 %
ESC
Motor 1
1
ESC
Parameter
1
set 1
ESC
Settings
3
OK
Display mea-
select
SIEMENS
Menu
3RW44
1
sured value
ESC
ESC OK
OK
select
Status
select
2
display
ESC OK
OK
OK
ESC
Starting
2
settings
ESC
Stopping
3
settings
OK
OK
OK
OK
OK
Slow-speed parameters
Note
To operate the motor with the specified slow speed parameters, the "Slow
speed" function must be assigned to one control input, and the "Motor
right PS1/2/3" or "Motor left PS1/2/3" function must at the same time be
assigned to the other. Also refer to the circuit suggestion in 9.1.7.
Directions of rotation:
Right: rotation in line phase direction
Left: rotation counter-clockwise to the line phase direction
select
select
sel ect
select
select
select
change
change
change