5.5.3 Motor Control (Assigning Control Priority)
ESC
Motor control
1
ESC
Motor
4
OK
ESC
Control motor
2
OK
change
ESC
Standard
3
OK
via inputs
control
Inputs
via keys
control
Notice
The "Standard control" menu item specifies which control device should be given
control priority when the control supply voltage is applied.
When the PROFIBUS communication module is activated, the setting is changed to
"Automatic/None".
Control device priority
Only a higher-priority control device can assume and hand over the control
priority (0 = lowest).
- 0: Automatic operation (input control through PLC via PROFIBUS)
- 1: PC via PROFIBUS (Soft Starter ES software required)
- 2: Inputs
- 3: Via display keys
- 4: PC via serial interface (Soft Starter ES software required)
ESC
Settings
3
Display mea-
select
SIEMENS
Menu
3RW44
1
sured value
ESC
ESC OK
OK
select
Status
select
2
display
ESC OK
OK
OK
Possible values
Activate key control?
Deactivate key control?
Execute control function
Activate control via inputs?
Deactivate control via inputs?
Automatic / None
Inputs
Keys
select
select
select
select