Installation, Connection and Branch Layout
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06
3-3
3.1.4 Mounting Dimensions and Clearances
For uninhibited cooling, aeration and de-aeration of the heat sink, it is essential
that the minimum clearance to other devices is strictly observed.
Figure 3-2: Clearance to other devices
Notice
Ensure that there is sufficient clearance so that air can freely circulate for
cooling. The device is ventilated from bottom to top.
1
1
3
5
2
46
5mm
[0.2 in]
5mm
[0.2 in]
100 mm
[4in]
75 mm
[3in]