PROFIBUS DP Communication Module
SIRIUS 3RW44 manual
8-52 GWA 4NEB 535 2195-02 DS 06
Device function
9
0-2
Reserved = 0
369 9
3
Basic factory settings restored The signal bit is always deleted after acknowledgement
with "Trip reset".
9
4-7
Reserved = 0
367 10 Faulty parameter number (low byte) In connection with byte 8
1
and 8
2
, states the ID number
of the first parameter not accepted.
The signal byte is always deleted after
acknowledgement with "Trip reset".
11 Faulty parameter number (high
byte)
12
0-1
Reserved = 0
1421 12
2
Impermissible Ie/CLASS settings
12
3-7
Reserved = 0
1449 13
0
Parameter set 1 active
1450 13
1
Parameter set 2 active
1451 13
2
Parameter set 3 active
13
3
Reserved = 0
1453 13
4
Impermissible change of the
parameter set
13
5-7
Reserved = 0
14
0-1
Reserved = 0
1404 14
2
Motor heating active
1402 14
3
DC braking active
1403 14
4
Dynamic DC braking active
1471 14
5
Motor connection method star/delta
1472 14
6
Motor connection method inside
delta
1473 14
7
Motor connection method unknown
1408 15
0
No load
15
1
Reserved = 0
1409 15
2
Loss of phase L1
1410 15
3
Loss of phase L2
1411 15
4
Loss of phase L3
1412 15
5
Line phase direction right
1413 15
6
Line phase direction left
15
7
Reserved = 0
16 Reserved = 0
1435 17
0
Output 1 active
1436 17
1
Output 2 active
1437 17
2
Output 3 active
1438 17
3
Output 4 active
ID
No.
Byte
Bit
Signal bit
E
No.
*)
Meaning/Acknowledgment