PROFIBUS DP Communication Module
SIRIUS 3RW44 manual
8-34 GWA 4NEB 535 2195-02 DS 06
Error types
The diagnosis message is reported on channel 0.
Table 8-14: Error types
E
No.
Error type Meaning/Cause Delete signal bit / Acknowledgement
E1
00001:
Short-circuit
Short-circuit in the temperature sensor
The signal bit is deleted automatically when
the cause for the switch-off has been
remedied and acknowledged via "Trip reset".
E4
00100:
Overload
Overload of the temperature sensor
Overload of the thermal motor model
The signal bit is updated continuously.
E5
00101:
Overtemperature
Overload of the contact block
The signal bit is deleted automatically when
the cause for the switch-off has been
remedied and acknowledged via "Trip reset".
E6
00110:
Line breakage
Wire break in the temperature sensor
The signal bit is updated continuously
E7
00111:
Maximum limit
value exceeded
•I
e
limit value exceeded
E8
01000:
Minimum limit
value undershot
•I
e
limit value undershot
E9
01001:
Error
Internal error/device error
Contact block defective
The signal bit can be deleted when the cause
of the error has been remedied by
Switching the supply voltage off/on
Issuing the "Restart" command if possible
E16
10000:
Parameter error
Incorrect parameter value
The signal bit is always deleted after
acknowledgement with "Trip reset".
E17
10001:
No supply or load
voltage
Electronics supply voltage too low
No supply voltage at the contact block
No line voltage
The signal bit is deleted when the cause for
the switch-off has been remedied or
acknowledged automatically.
E24
11000:
Actuator switch-
off
Switch-off due to overload
Switch-off due to residual current
Switch-off due to asymmetry
Switch-off due to ground fault
The signal bit is always deleted after
acknowledgement with "Trip reset".
Additional acknowledgement in combination
with other errors.
E26
11010:
External error
Overload of the sensor supply
Process image error
The signal bit is always deleted after
acknowledgement with "Trip reset".