PROFIBUS DP Communication Module
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06
8-39
Error codes
The following error codes are generated by the soft starter:
Table 8-15: Error codes
Error codes 
byte
Error message Cause
High Low
00 
H
00 
H
No error
Communication interface
80 
H
A0 
H
Negative acknowledgement
"Read data set"
• Data set can only be written
80 
H
A1 
H
Negative acknowledgement
"Write data set"
• Data set can only be read
80 
H
A2 
H
Protocol error • Layer 2 (field bus)
• Device interface
• Incorrect coordination
80 
H
A9 
H
This function is not supported! • DPV1 service does not 
support reading/writing of the 
data set
Technology access
80 
H
B0 
H
Unknown data set number • Data set number not known in 
the soft starter
80 
H
B1 
H
Incorrect data set length when writing • Data set length differs from 
data set length specified
80 
H
B2 
H
Incorrect slot number • Slot number not 1 or 4
80 
H
B6 
H
Communication partner declined data 
acceptance!
• Incorrect operating mode 
(automatic, manual bus, 
manual operation local)
• Data set can only be read
• Parameter changes not 
permissible when ON
80 
H
B8 
H
Invalid parameter • Incorrect parameter value
Device resources
80 
H
C2 
H
Temporary lack of resources in the 
device!
• No available receive buffer
• The data set is currently being
updated
• The data set order is currently 
active at another interface