PROFIBUS DP Communication Module
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06
8-65
163 96 Output 1 - Action x • No action (default) [0]
• Control source PIO-DO 1.0 
output 1 [1]
• Control source PIO-DO 1.1 
output 2 [2]
• Control source input 1 [6]
• Control source input 2 [7]
• Control source input 3 [8]
• Control source input 4 [9]
• Run up [10]
• Operation / bridging [11]
• Stopping [12]
• On-time motor [13]
• Control command MOTOR ON 
[14]
• Fan [15]
• DC braking contactor [16]
• Device - ON [18]
• Group warning [31]
• Group error [32]
• Bus error [33]
• Device error [34]
• Ready for motor on [38]
164 97 Output 2 - Action (refer to Output 1 - Action) x
165 98 Output 3 - Action (refer to Output 1 - Action) x
166 99 Output 4 - Action
100 -
111
Reserved = 0
116 112 Breakaway time 0 ... 2 s [0 ... 200] 0.01 s
117 113 Breakaway voltage 40 ... 100 % [8 ... 20] 5 %
169 114 -
115
Maximum starting time 0 ... 1, 000 s [0 ... 10,000] 0.1 s
170 116 -
117
Starting time 0 ... 360 s [0 ... 3,600] 0.1 s
171 118 -
119
Stopping time 0 ... 360 s [0 ... 3,600] 0.1 s
172 120 Start torque 10 ... 100 % [2 ... 20] 5 %
118 121 Limiting torque 20 ... 200 % [4 ... 40] 5 %
173 122 Stopping torque 10 ... 100 % [2 ... 20] 5 %
123 Reserved = 0
124 Reserved = 0
119 125 Motor thermal capacity 1 ... 100 % [1 ... 100] 1 %
126 -
129
Reserved = 0
178 130 Dynamic braking torque 20 ... 100 % [4 ... 20] 5 %
ID 
No.
Byte
Bit
Meaning
Only for 
data set 
131
Value range [coding] Factor