Commissioning
SIRIUS 3RW44 manual
5-14 GWA 4NEB 535 2195-02 DS 06
"Voltage ramp" starting mode
Figure 5-8: "Voltage ramp" starting mode
change
ESC
Starting mode
1
ESC
Starting
2
OK
settings
Voltage ramp
OK
ESC
Start voltage
2
40.0 %
OK
ESC
Starting time
5
20 s
OK
ESC
Maximum
6
deactivated
OK
starting time
ESC
Breakaway
8
80 %
OK
voltage
ESC
Breakaway time
9
0 ms
OK
4_1_Menü_Startart_Spannungsrampe.wmf
Adjustable
from ... to
20 ... 100 %
0 ... 360 s
1 ... 1,000 s
40 ... 100 %
0 ... 2,000 ms
ESC
Motor 1
1
ESC
Parameter
1
set 1
ESC
Settings
3
OK
Display mea-
select
SIEMENS
Menu
3RW44
1
sured value
ESC
ESC OK
OK
select
1
Status
select
2
display
ESC OK
OK
OK
OK
OK
select
select
select
select
change
change
change
change
change
Voltage in %
U
Motor
100 %
Breakaway voltage
Start voltage
Breakaway time
starting time
Maximum starting time
100 % Voltage
at the motor
Time (t)
s