Line Modules Booksize
4.3 Active Line Modules with internal air cooling
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
169
7TE25–5AA3 +
Active Interface
Module
Rated short-circuit current
SCCR
3)
kA 65 65 65 65
4)
See Chapter Combination options, Line Modules with line reactors
and line filters (Page 135)
(internal air cooling) Internal fan Internal fan Internal fan Internal fan
Max. permissible heat sink tempera-
ture
° C 85 90 83 83
3
Rated voltage for rated data 3 AC 380 V
The specified power ratings apply to the line voltage range from 380 V to 480 V.
Default for 400 V line systems; undervoltage trip threshold is adjusted to the parameterized rated voltage
The resulting rated short-circuit current is obtained from the combination of the fuse or circuit breaker – and the Line
Module in the drive system.
4)
Maximum total cable length = Σ motor cables, line feeder cable from line filter to the Line Module
Table 4- 11 Technical data for Active Line Modules with internal air cooling, part 2
1)
Rated power S1 duty
Infeed power S6 duty (40 %)
kW (P
n
)
kW (P
S6
)
80
106
120
145
Continuous regenerative power
kW
80
120
Line voltage
Line frequency
V
ACrms
Hz
DC
3 AC 380 … 480 ±10 % (-15 % < 1 min)
47 … 63
DC link voltage
Overvoltage trip
2)
V
DC
V
DC
510 … 720
820 ± 2 %
Rated input current:
for AC 400 V
input current:
for AC 380 V / AC 480 V
for AC 400 V; S6 duty (40 %)
for AC 400 V; peak current
A
AC
A
AC
A
AC
AC
122
128 / 102
161
182
192 / 152
220