Planning
42
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
Monitored control line 2
The monitored control line 2 is provided for connecting either:
A remote transmission device
A fire control
An additional alarm horn
An additional warning panel
Fig. 28 Monitored control line 2, programming step 3
In programming step 3, you can select the following functions:
Option 17: For remote transmission, active on "RT-alarm"
Option 18: For fire control, active on state "Fire alarm"/"Activated"/"Released"
Option 19: For fire control, active on state "Activated"/"Released"
Option 20: For alarm horn, active on state "Fire alarm"/"Activated"/"Released"
1
)
Option 21: For alarm horn, active on state "Activated"/"Released"
1
)
Option 22: For warning panel, active on state "Mech. blocked"
Option 23: For warning panel, active on state "Autom. & Man. blocked"
Option 24: For warning panel, active on state "Manual only" or "Autom. & Man.
blocked"
1
) Continuous tone until "Silence Re-sound horn" or "Reset"
In the basic configuration, control line 2 is set to be active on state "RT-alarm" to
"Reset" (= option 17)
Details on programming, see chapter 11.6.3