Planning
43
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
Monitored control line 3
The monitored control line 3 is provided for the connection of illuminated warning
panel to signal the release of gas.
Fig. 29 Monitored control line 3, programming step 5
In programming step 5 you can set the active mode and the active duration of the
warning panel using options 15 to 25 as follows:
Fire alarm: Option 15 = Not activated
Option 16 = Continuous
Option 17 = Pulsating fast
Activated: Option 18 = Continuous
Option 19 = Pulsating fast
Released: Option 20 = Continuous until "Reset"
Option 21 = Continuous until "Silence Re-sound horn" or "Reset"
Option 22 = Continuous until "Digit KEY4" is pressed after "Reset"
Option 23 = Pulsating fast until "Reset"
Option 24 = Pulsating fast until "Silence Re-sound horn" or "Reset"
Option 25 = Pulsating fast until "Digit KEY4" is pressed after "Reset"
In the basic configuration, the warning panel is set so that it is not activated in the
"Fire alarm" condition and continuously lit in the "Activated" and "Released"
conditions until "Reset" (= option 15 + 18 + 20).
Details on programming, see chapter 11.6.5
Monitored control line 4
Monitored control line 4 is provided for connecting the extinguishing release
element (pyrotechnical actuator or solenoid).
Fig. 30 Monitored control line 4, programming steps 1 and 2
In programming steps 1 and 2 you can set the activated time and the flooding time
of the control line 4 as follows:
The activated time is set in programming step 1, options 1 to 13, and
The flooding time is set in programming step 2, options 1 to 5