Chapter 4 Service Procedure
HRS Series 4.5 Replacement Procedure
Mounting
1. Mount the marking tie at approx. 40+/-5mm away from the cable end.
2. Remove the nut of the level switch.
3. Mount the nut after mounting the level switch to the tank. (Nut ×1)
Fig. 4.5-14 Mount of level switch
[Tips]
The marking part of the level switch faces upward.
4. Put the level switch cable [LS1] (2pcs.) through the grommet. Insert the pin to the connector.
(No.2 & No.13)
Fig. 4.5-15 Location to mount the connector
[Tips]
It does not matter which connector [LS1] is mounted to which socket.
5. Mount the upper panel and the side panel on the left in reversed order of removal.
6. Mount the lid of the tank.