HRS Series 6.1 Specifications List
Chapter 6 Documents
6.1 Specifications List
Table 6-1 Specifications List (HRS01--10-(BJMT))
Air-Cooled
refrigerated type
Water-Cooled
refrigerated type
Air-Cooled
refrigerated type
Water-Cooled
refrigerated type
Ambient temperature and humidity
2
Temperature :5 to 40
o
C, Humidity:30 to 70%
Tap water, Ethylene glycol aqueous solution 15%
5
Operating temperature range
2
Cooling capacity
4
(50/60Hz)
Pump capacity
7
(50/60Hz)
0.13(at 7L/min) / 0.18(at 7L/min)
For option -T, -MT: 0.36(at 7L/min) / 0.42(at 10L/min)
7/7
For option -T, -MT: 7/10
Stainless steel, Copper brazing (Heat exchanger)
15
, Bronze
15
Brass
15,
SIC,Aluminum oxide ceramic, Carbon, PP, PE, POM, FKM, EPDM, PVC
Facility water
outlet system
1
Facility water pressure differential
Stainless steel, Copper brazing, Bronze, Synthetic rubber
Automatic
fluid filling
14
Feed water pressure range
Feed water temperature range
Automatic fluid filling Port size
1-phase AC100V 50Hz, 1-phase AC100 to 115V 60Hz.
Allowable voltage range ±10%
Applicable earth leakage breaker capacity
9
Rated operating current
4
(50/60Hz)
7.5/8.3
For option -T, -MT: 9.8/10.6
7.7/8.4
For option –T, -MT: 10.0/11.0
Rated power consumption
4
(50/60Hz)
0.7/0.8
For option -T, -MT: 1.0/1.1
0.8/0.8
For option -T, -MT: 1.0/1.1
W377xD500xH615 (W14.8XD19.7xH24.2[Inch])
Fitting (for drain port) 1pc.
16
, Sequence I/O command
signal connector 1pc., Power supply connector 1pc., Operation manual
(Installatio・Operation) 1pc, Quick manual (with a clear cover) 1pc., Alarm code
list label 1pc.
1 For water -cooled type.
2 Use the product in conditions where freezing will not occur.
Consult with SMC if using in a season or region where the ambient temperature will fall below zero.
3 If tap water is used, use water which satisfies the standard of The Japan Refregeration And Air Conditioning Industry Association (JRA GL-02-1994/Cooling water
system - circulation type - make-up water)
4 (1)Operating ambient temp.: 25°C, (2)Circulating fluid temp.: 20°C, (3)Circulating fluid rated flow, (4)Criculating fluid : Tap water,(5)Facility water temp.: 25°C.
The cooling capacity will be reduced by 300W when option T and MT [High pressure pump] are selected.
5 Use a 15% ethylene glycol aqueous solution if operating in a place where the circulating fluid temp. is lower than 10
o
C.
6 Outlet temp. when the circulating fluid flow is rated flow, and the circulating fluid outlet and the return are directly connected. Installation environment and power supply
are within specification range and stable.
7 The capacity at the thermo-chiller outlet when the circulating fluid temp. is 20°C.
8 Fluid flow to maintain the cooling capacity and the temperature stability.
The specification of the coolong capacity and the temperature stability may not be satisfied if the flow rate is lower than the rated flow.
9 To be prepared by the customer. Use an earth leakage breaker with sensitivity of 15mA or 30mA/100V in power
supply specification.
10 Front 1m/Height 1m/Static with no load. See note 3 for other conditions.
11 Dimension between panels. Projection is not included.
12 Weight when the circulating fluid and facility water (for water-cooled type) is not included.
The weight will increase by 1kg when option J [Automatic fluid filling] is selected. The weight will increase by 4kg when option T and MT [High pressure pump] are
selected.
13 There is required flow when adding load described on cooling capacity in case of note 4 conditions.
14 For option J [Automatic fluid filling port].
15 Copper, bronze and brass are not included when option M [DI water piping] is selected.
16 This fitting is not included when option T and MT [High pressure pump] are selected.
17 If option “Earth leakage breaker type” is selected, the earth leakage breaker is used instead of the circuit protector.