EasyManua.ls Logo

SMC Networks HRS012-A-10 Series - 6.4 Flow chart

SMC Networks HRS012-A-10 Series
222 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HRX-MM-N007
Chapter 6 Documents
HRS Series 6.4 Flow chart
6-7
6.4 Flow chart
6.4.1 HRS012-A-, HRS018-A-, HRS024-A-20, HRS030-A-20
Ventilation Ventilation
Circulating fluid circuit
Refrigeration circuit
Tank
Level switch
Comp
Press sensor
for high pressure
Expansion1
Expansion2
Temp sensor
Press sensor
for low pressure
Temp sensor
for return port
Pump
Press sensor
for outlet
Temp sensor
for outlet
Circulating fluid outlet
Rc1/2
Filter
Drain port
Circulating
fluid return port
Rc1/2
Solenoid valve for
automatic fluid filling
Automatic
fluid filling port
Rc3/8
Over flow port
Rc3/4
Air-cooled
condenser
Heat exchanger
Automatic fluid filling circuit
(For option with automatic
fluid filling)-J
Fig. 6.4-1 Flow chart (HRS012-A-HRS018- A-HRS024-A-20HRS030-A-20)
6.4.2 HRS012-W-, HRS018-W-, HRS024-W-20, RS030-W-20
Circulating fluid circuit
Refrigeration circuit
Tank
Level switch
Comp
Press sensor
for high pressure
Expansion1
Expansion2
Temp sensor
Press sensor
for low pressure
Temp sensor
for return port
Pump
Press
sensor
for outlet
Temp sensor
for outlet
Circulating
fluid return port
Rc1/2
Circulating fluid
outlet
Rc1/2
Drain
port
Filter
Facility water circuit
Water regulating
valve
Facility water
outlet
Rc3/8
Facility
water inlet
Rc3/8
Plug
Solenoid valve for
automatic fluid filling
Automatic fluid
filling port
Rc3/8
Over flow port
Rc3/4
Automatic fluid filling circuit
(For option with automatic
fluid filling)-J
Water-cooled
condenser
Heat exchanger
Fig. 6.4-2 Flow chart (HRS012-W-HRS018-W-HRS024-W-20HRS030-W-20)

Table of Contents