EasyManuals Logo

SMC Networks HRS012-A-10 Series User Manual

SMC Networks HRS012-A-10 Series
222 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #192 background imageLoading...
Page #192 background image
HRX-MM-N007
Chapter 4 Service Procedure
4.5 Replacement Procedure HRS Series
4-56
Removal (Between tank-heat exchanger)
1. Discharge the circulating fluid referring the 4.2.2 Discharge of the circulating fluid and
facility water.
2. Remove the upper panel and the side panel on the left referring the 4.2.1 Removal and the
mounting of the panel.
3. Remove the hose clamp on the tank side. (2 locations)
4. Remove the tank.
5. Remove the hose clamp on the heat exchanger side and remove the hose.
Fig. 4.5-41 Removal of plastic hose (Between tank-heat exchanger)
Mounting (Between tank-heat exchanger)
1. Mount the hose on the tank using the hose clamp.
2. Install the tank.
3. Mount the hose on the heat exchanger.
4. Hold the hose with the hose clamp. (3 locations)
5. Mount the upper panel and the side panel on the left in reversed order of removal.
2. Hose clamp
2. Hose clamp
2. Hose
2. Hose
Tank
Heat exchanger
Check the hose is not twisted after connecting.