EasyManua.ls Logo

SMC Networks HRS012-A-10 Series - Page 98

SMC Networks HRS012-A-10 Series
222 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HRX-MM-N007
Chapter 3 Alarm Indication and Troubleshooting
3.3 Troubleshooting HRS Series
3-82
6. Check for an input to the pressure sensor in the refrigerant circuit.
Check that the power is supplied to the refrigerant circuit pressure sensor.
Check voltage by contacting the probe of the tester directly to the connector external surface with
the "CN4" connector of the main board being inserted.
<Refrigerant circuit pressure sensor (for low pressure)>
Contact the positive probe to the pin number 24 and contact the negative probe to the pin number
12 of the "CN4" connector.
<Normal> Pin number 24 - Pin number 12: Voltage should be 5 VDC +/- 1V
Fig. 3.3-58 Check of the refrigerant circuit pressure sensor (for low pressure) input