40
General Operation Installation & Configuration Guide for MAXPage
Open: The alarm input is normally open message is sent when input closes.
Close: The alarm input is normally closed message is sent when input opens.
On Change: A message is sent when the alarm changes to or from any state.
7. Press the key to move along to the next field.
8. The next field along is Delay. This specifies the delay in seconds (between 0-999) before a message is sent.
If the alarm state returns to the previous state before the delay period, no message is sent. E.g.: You could
wire an alarm input to a freezer door so people do not forget to close it. Give it a delay of 60 seconds. If the
freezer door is open more than 60 seconds a message is sent. If it is closed within 60 seconds no message
will be sent.
9. Press the key to move along to the next screen.
10. The first field on the next screen is 1
st
Pager. This field refers to the Pager ID of the first recipient that
receives the message. Enter a valid Pager I.
11. Press the key to move along to the next field.
12. The next field along is Escalation. If you want the alarm to escalate to a second recipient after a certain
amount of time if it is still active, enter an escalation time here between 1 999 seconds.
13. Press the key to move along to the next field.
1
st
Pager [ ]
Escalation [ ]
14. The next field is 2
nd
Pager. This refers to the Pager ID of the second recipient that receives the message if
the alarm is still active after the escalation time. This is useful for notifying managers if alarms are not
cleared after some time.
15. Press the key to move along to the next field.
2
nd
Pager [ ]
Call Tone [C]
16. The next field along is Call Tone. Press any key on the keypad to choose between A, B, C, or D. This is the
beep code that is sent with the message.
17. Press the key to move along to the next field.
Send ResetMsg[Y]
18. The field on this screen is Send ResetMsg. By default, the MAXPage unit sends a reset message when an
alarm is reset back to its normal state. The ability for this reset message to be sent can be toggled with this
setting.
19. Press the key to save changes. You are taken back to the first screen of the Add/Edit Alarm Menu.
20. To return to Normal Mode, press the key three times to exit out of all menus. MAXPage restarts and
can be used.
Delete Alarm
1. To select Delete Alarm press from the Alarms Menu.